A. ALL SLABS ON GRADE SHALL CONSIST OF A 4 INCH THICK 2500 PSI (MIN) SLAB PLACED OVER A 6

Board of Adjustments Regular Meeting · 2026-04-21 · agenda_item

This item concerns proposed construction standards for concrete slabs on grade. The specifications call for a 4-inch thick slab with a minimum strength of 2500 PSI. It will be placed over a minimum 6-mil polyethylene vapor retarder, which itself will be laid on clean, compacted fill. The concrete must be reinforced with polypropylene fibers, at least 1-1/2 inches long, at a rate of 1.5 pounds per cubic yard of concrete. All vapor retarder edges must overlap by at least 6 inches and be taped at joints and penetrations. This item is currently under review by the Board of Adjustments. If approved, this project would involve site preparation, concrete pouring, and potentially utility work. Contractors specializing in concrete, site preparation, and potentially underground utilities could find opportunities. Engaging early before final permits are issued may offer a competitive advantage.

slab thickness
4 inch
minimum concrete strength
2500 PSI
minimum vapor retarder thickness
6 mil
minimum fiber length
1-1/2 inch
fiber rate
1.5 lbs/CY
minimum vapor retarder overlap
6 inch